Power transformer OLSPU-1,25

Power transformer OLSPU-1,25 is designed for installation in complete switchgear units (CSU) of internal and external installation to provide power supply to auxiliary circuits of sectionalization points and automatic transfer switch (ATS). Transformers are used in AC installations at power generation facilities in industry, agriculture, the public utilities sector and other sectors of the national economy.

The transformer is manufactured in the U version of the placement category 2 according to GOST 15150-69 and is designed to operate in the following conditions:

  • height above sea level - no more than 1000 m;
  • relative air humidity not more than 98% at 30 °C;
  • upper operating value t0 of the environment + 50 °C;
  • lower operating value t0 of the environment -45 °C;
  • ambient environment - non-explosive, free of dust, chemically active gases and vapors in concentrations that destroy metal coatings and insulation (type II atmosphere according to GOST 15150-69);
  • any position of transformers in space.

Technical specifications comply with DSTU EN 60076-1, DSTU EN 60076-11.

  • Survey letter
  • Contact a specialist

Technical specifications

Parameter nameParameter value
Maximum equipment voltage, Um, kV3.6; 7.2; 12
Rated power, VA1250
Nominal voltage of the primary winding, Un1, kV3.0; 3.3; 3.6; 6.0; 6.3; 6.6; 10; 10.5; 11
Operating voltage range, % of rated voltage± 20
Nominal frequency, Hz50
Rated voltage of the secondary winding, Un2, V- X-A1- X-A2- X-A3- X-A4100 ± 5 9 ± 5 "0 ± 5 #1 ± 5 %
No-load current, %, not more than4
Winding connection diagram and group1/1-0
Test voltage of primary winding insulation for 1 min, kV42
Test insulation voltage of the secondary winding for 1 min, kV3
Overload capacity2 х Pном/10 минут
Weight, kg, not more than35

OVERALL, INSTALLATION, CONNECTION DIMENSIONS AND SCHEMATIC DIAGRAM OF TRANSFORMER OLSPU-1.25



Application form!
send
This form is for sending a request for a call back.
Contacts
  • +38 098 606-33-15
  • Dnipro CityAddress
  • Schedule
  • comerc@elemark.com
  • ©ELEMARK2025

Pages
  • Ноme
  • Products
  • Certificates
PRODUCTS
  • Measuring transformers
  • Power transformers
  • Current transformers
  • Switching pads
Powered By Blade.MSP ® from BrainTEC ™