  4. Current transformer TZLU-205-1

Current transformer TZLU-205-1

The current transformer TZLU-205-1 is a monolithic product with a window through which a three-core cable is passed. This model provides for the passage of a cable with a diameter of up to 205 mm, as indicated by its marking. When currents up to 10 kV pass through the cable, its outer metal sheath and armor must be grounded.

If a short circuit occurs between individual cable cores, the zero sequence is broken, the passing currents form a magnetic field, and a voltage is generated in the transformer. This voltage is transmitted to the connected protective relay, which immediately trips. In addition to the relay, it is possible to connect signaling and automation equipment, control devices.

The product belongs to category 2 (indoor or under a canopy) and is manufactured in climatic version "U" (temperate climate zone).

  • Survey letter
  • Contact a specialist

Technical specifications

Parameter nameValue
Rated voltage, kV0,66
Note. When installing a cable with a rated operating voltage of 10 kV (maximum 12 kV), the main insulation between the current-carrying conductors of the cable and the secondary winding of the transformer is provided by the cable insulation, while the metal sheath and cable armor must be grounded.
Rated frequency, Hz50
Number of secondary windings1
Transformation ratio30/160/1
Rated primary current, A3060
Maximum primary current, A60250
Rated current strength of the secondary winding, A11
Rated load of the secondary winding at cos φ = 1, Ohm11
Limit of error of the secondary winding at rated load: - current, %, not more than; - angular, o, not more thanf = 1,5 %
δ = 3
f = 1 %
δ = 1
Sensitivity: on S1-S2 at rated load and primary current of 0.25 A, not less than, mV84
1 sec thermal resistance current of the secondary winding, A150
Test one-minute insulation voltage, kV3
Weight, kg5.7
Stability of characteristics, at least, years50
Warranty period, years5
Guaranteed storage life, years3

Notes. 1) The error is normalized in the current range from 1% of the rated current to the maximum primary current at rated load. 2) When the rated load is reduced, the transformer error decreases and the current range expands. 3) The primary current sensitivity of the protection is determined by the expression: (primary current, A) = (installation current, A) * (transformation ratio), taking into account the transformer error and the error of the relay used.

At the customer's request, transformers can be manufactured with a different transformation ratio. The winding of the transformers is made on a nanocrystalline alloy core. This ensures a large linear dynamic range of winding characteristics in terms of current and angle. This ensures long-term stability of the characteristics throughout the entire service life of the transformer and the resistance of the magnetic circuit to magnetization (from unipolar pulse short-circuit currents of a three-phase cable). In addition, a safety factor of no more than three is provided, which significantly reduces emergency overloads of measuring devices connected to the secondary winding. The use of these transformers reduces operating costs for consumers.

Application form!
send
This form is for sending a request for a call back.
Contacts
  • +38 098 606-33-15
  • Dnipro CityAddress
  • Schedule
  • comerc@elemark.com
  • ©ELEMARK2025

Pages
  • Ноme
  • Products
  • Certificates
PRODUCTS
  • Measuring transformers
  • Power transformers
  • Current transformers
  • Switching pads
Powered By Blade.MSP ® from BrainTEC ™