  5. Current transformer TOPA-0,66-B

Current transformer TOPA-0,66-B

Current transformer TOPA 0,66-B is used in AC installations operating in climatic conditions "U". It allows taking readings of the level of the electrical signal using measuring instruments. Such transformers are installed at electric power facilities operated in various sectors of the national economy: industrial, agricultural, municipal, etc. The rules for the placement of transformers are established by DSTU 15150-69. They work in any position. The material for their measuring winding is a nanocrystalline alloy. Its use makes it possible to take characteristics in a wider linear dynamic range, even if the currents are less than 1%. At the same time, long-term stable characteristics are achieved throughout the entire service life of the transformer, and the magnetic circuit remains insensitive to the effects of short-circuit currents that can lead to magnetization by unipolar pulses.

  • Survey letter
  • Contact a specialist

Verification interval 16 years

Type examination certificate (module B) No. UA.TR.001 103-18 Rev 1. Reference number 29/3/B/12/114-20. Conforms to DSTU EN 61869-2:2017, TU U 31.1-34562687-001:2007 Industrial design patent No. 17817.

Technical specifications

Parameter nameValue
Rated voltage, kV0.72
Rated primary current, A400, 500, 600, 800, 1000
Rated secondary current, A5
Rated frequency, Hz50
Accuracy class no more than0.5S
Nominal safety factor of FS devices, not more than3
Rated secondary load at cos φ = 0.8, VxA5
Rated insulation level, kV3

The transformer in operation is subject to periodic verification according to the methodology of DSTU 6097: 2009 at least once every sixteen years. The design of the transformer allows it to be mounted on a DIN rail using the supports included in the delivery. Wires with a cross-section of up to 6 mm2 can be connected to the secondary winding contacts S1, S2. It is possible to connect the wires from one of the two sides of the housing, while access to the contacts on the opposite side is blocked by a cover. Each wire is clamped with two screws.

Application form!
send
This form is for sending a request for a call back.
Contacts
  • +38 098 606-33-15
  • Dnipro CityAddress
  • Schedule
  • comerc@elemark.com
  • ©ELEMARK2025

Pages
  • Ноme
  • Products
  • Certificates
PRODUCTS
  • Measuring transformers
  • Power transformers
  • Current transformers
  • Switching pads
Powered By Blade.MSP ® from BrainTEC ™