Current transformer TOLU-10-3

The current transformer TOLU-10-3, which you can order in our catalog, is used in switchgears.

It is manufactured in the climatic version "U", which means it is suitable for use in temperate climates.

It can be placed in any position outside and inside buildings (location category 1.2).The principle of operation is to convert the high voltage of the mains current to the parameters acceptable for taking measurements. The output of the transformer can be connected to measuring equipment, automation, and control devices. It also protects secondary circuits from high voltage.

The durability and quality of operation are ensured by the secondary winding core made of an innovative material. A nanocrystalline alloy is used for this purpose. This material does not experience magnetization under the influence of passing currents.

Thus, the output current parameters are not distorted, and the device itself retains its original metrological properties for a long time (50 years).

  • Survey letter
  • Contact a specialist

Type examination certificate (Module B) No. UA.TR.001 150-19 Rev.2, reference number 29/3/B/12/016-20. Complies with DSTU EN 61869-2:2017.

Technical specifications

Parameter nameValue
Rated voltage kV10
Maximum operating voltage, kV12
Rated primary current, A5, 10, 15, 20, 30, 40, 50, 75, 100, 150, 200, 300, 400, 500, 600, 800, 1000, 1500, 2000, 2500, 3000
Rated secondary current, A1;5
Rated frequency, Hz50
Number of windings2; 3; 4
Accuracy class of the secondary winding: - for measurement; - for protection;0,2S; 0,5; 0,5S; 0,5S+ / 5Р; 10P
Rated secondary load at cos φ = 0.8, VxA winding: - for measurement; - for protection;10/15
Rated primary current, A51015203040507510015020030040050060080010001500200025003000
Rated short-term thermal resistance current, Ith, kA0,61,31,32,63,33,33,77,77,414,414,428,828,836368686108108108108
Rated current strength of dynamic stability Idyn, kA1,63,33,36,58,38,39,318,518,5363672729090215215270270270270
Safety factor of the device, FS, not more than333333333333334555555
Ultimate accuracy factor, ALF, not less than **7777788787878899910131313

The transformer can be supplied with a cover to protect the secondary winding terminals from unauthorized access (sealing) - if specified in the supply contract.

* Transformers with a nominal secondary load of up to 30 V-A can be supplied (please specify when ordering).

** Transformers with a maximum accuracy factor of at least 10 can be supplied (specify when ordering).

Application form!
send
This form is for sending a request for a call back.
Contacts
  • +38 098 606-33-15
  • Dnipro CityAddress
  • Schedule
  • comerc@elemark.com
  • ©ELEMARK2025

Pages
  • Ноme
  • Products
  • Certificates
PRODUCTS
  • Measuring transformers
  • Power transformers
  • Current transformers
  • Switching pads
Powered By Blade.MSP ® from BrainTEC ™