Current transformer TOLU-10

The current transformer TOLU-10 changes the initial current parameters to values that can be measured by measuring devices. Automation devices and relay protection circuits can also be installed at their output.


With its help, secondary circuits are isolated from the high voltage received from the mains. This ensures the safety of their operation. Such transformers are installed in AC switchgear devices.


They operate with a voltage of up to 10 kV. The current frequency is 50 Hz. Their manufacture corresponds to climatic execution "U" 2. Production technologies provide for compliance with the requirements of DSTU 15150-69. The main reason to buy it is the quality of work and durability ensured by the use of nanocrystalline materials in the manufacture of the core. It does not lend itself to magnetization and allows the device to operate for 50 years without changing its metrological characteristics.

  • Survey letter
  • Contact a specialist
Type examination certificate (Module B) No. UA.TR.001 150-19, reference number 29/3/B/12/227-18. Complies with DSTU EN 61869-2:2017, TU U 31.1-34562687-001:2007.

Technical specifications

Parameter nameValue
Rated voltage kV10
Maximum operating voltage, kV12
Rated primary current, A5, 10, 15, 20,25, 30,40, 50, 75,80, 100, 150, 200, 250, 300, 400, 500, 600, 700, 750, 800, 1000
Rated secondary current, A1;5
Rated frequency, Hz50
Accuracy class of the secondary winding: - for measurement; - for protection;0,2S; 0,5; 0,5S; 0,5S+ / 5Р; 10P
Rated secondary load at cos φ = 0.8, V-A winding: - for measurement; - for protection;10/15
Rated primary voltage, A5101520304050751001502003004005006008001000
Rated short-term thermal resistance current, Ith, kA0,61,31,32,63,33,33,77,77,414,414,428,828,836368686
Rated current strength of dynamic stability Idyn, kA1,63,33,36,58,38,39,318,518,5363672729090215215
Safety factor of the device, FS, not more than33333333333333455
Ultimate accuracy factor, ALF, not less than **77777887878788999


It is possible to supply a cover for protection of the secondary winding terminals against unauthorized access (sealing) in the transformer package - if specified in the supply contract. It is possible to manufacture transformers with size C - 65 or 80.* It is possible to supply transformers with a rated secondary load of up to 30 V-A (specified when ordering).** It is possible to supply transformers with a rated maximum multiplicity of at least 10 (specified when ordering). We work with the technical specifications.

Application form!
send
This form is for sending a request for a call back.
Contacts
  • +38 098 606-33-15
  • Dnipro CityAddress
  • Schedule
  • comerc@elemark.com
  • ©ELEMARK2025

Pages
  • Ноme
  • Products
  • Certificates
PRODUCTS
  • Measuring transformers
  • Power transformers
  • Current transformers
  • Switching pads
Powered By Blade.MSP ® from BrainTEC ™