Bushings current transformer TPLKU-10

Transformers are designed for installation in complete switchgear and are used to transmit measurement information signals to measuring instruments and protection, automation and control devices in AC installations for voltage classes up to 12 kV with a frequency of 50 Hz.

The transformers are manufactured in climatic version "U" of location category 2 according to GOST 15150-69. The operating position is any. The cores of the winding for measurements are made of nanocrystalline alloy, which guarantees the preservation of metrological characteristics for 50 years and excludes the possibility of core magnetization.

  • Survey letter
  • Contact a specialist
Complies with DSTU EN 61869-2:2017.

Technical specifications

Parameter name

Value

Rated voltage, kV

10

Maximum operating voltage, kV

12

Rated primary current, A

10, 15, 20, 30, 40, 50, 75, 100, 150, 200, 300, 400, 500, 600, 800, 1000, 1500, 2000, 2500, 3000

Rated secondary current, A

5

Number of secondary windings

3

Rated frequency, Hz

50

Accuracy class of the secondary winding: - for measurement;

- for protection

0,2; 0,2S; 0,5; 0,5S

10Р

Nominal secondary load at cos φ = 0.8, V x A winding: - for measurement;

- for protection.

10 *

15

Rated safety factor of winding instruments for transformer measurements for rated primary current: - ≤ 600 A, not more than

- ≥ 800 A, not more.

3;

5;

one-minute test voltage of industrial frequency:

- primary winding, kV;

- secondary winding, kV.

42

3

Rated primary current, A

10

15

20

30

40

50

75

100

150

200

Rated short-term thermal resistance current, not more than, kA

1,3

2,3

2,6

3,3

3,3

3,7

7,7

7,4

14,4

14,4

Electrodynamic stability current, kA

3,3

5,8

6,5

8,3

8,3

9,3

18,5

18,5

36

36

Nominal maximum winding multiplicity for protection, not less than **

7

7

7

7

8

8

7

8

7

8

Rated primary current, A

300

400

500

600

800

тисячі

1500

2000

2500

3000

Rated short-term thermal resistance current, not more than, kA

28,8

28,8

36

36

86

86

108

108

108

108

Electrodynamic stability current, kA

72

72

90

90

215

215

270

270

270

270

Nominal maximum winding multiplicity for protection, not less than **

7

8

8

9

9

9

10

13

13

13

It is possible to supply a cover to protect the secondary winding terminals from unauthorized access (sealing) - if specified in the supply contract.

* - It is possible to supply transformers with a nominal secondary load of up to 30 V - A (specified when ordering).

** - Transformers with a nominal maximum multiplicity of at least 10 can be supplied (specify when ordering).

Application form!
send
This form is for sending a request for a call back.
Contacts
  • +38 098 606-33-15
  • Dnipro CityAddress
  • Schedule
  • comerc@elemark.com
  • ©ELEMARK2025

Pages
  • Ноme
  • Products
  • Certificates
PRODUCTS
  • Measuring transformers
  • Power transformers
  • Current transformers
  • Switching pads
Powered By Blade.MSP ® from BrainTEC ™